fire code, O. Reg. 213/07

Section 4.3.16.2

Cite as fire code, O. Reg. 213/07, s. 4.3.16.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) In addition to the requirements of Article 4.3.16.1., when underground storage tanks have no further use or have been out of service for two years or longer, such tanks, together with connected piping and dispensers, shall (a) have all flammable liquids and combustible liquids removed from them, (b) be purged of vapours, and (c) except as permitted in Article 4.3.16.3., be removed from the ground. (2) If contaminated, soil surrounding the storage tanks described in Sentence (1) shall be replaced with clean fill. Abandonment in place
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.