The text
(1) Where a leakage test incorporating a liquid test medium, including a petroleum product, is performed on an underground storage tank, the tank shall be considered to be leaking when, with compensation for volume differentials caused by the effects of temperature and tank shell distortion, the test indicates a liquid loss greater than 0.189 litres per hour.
(2) The pressure at the bottom of a storage tank shall not exceed seventy kilopascals above atmospheric pressure during the leakage test referred to in subsection (1).
Read the Petroleum Product Storage and Handling on the Province's website ↗
Made under Clean Environment Act, c. C-6.