Petroleum Product Storage and Handling, N.B. Reg. 87-97
Section 65
Cite as Petroleum Product Storage and Handling, N.B. Reg. 87-97, s. 65 · current to June 13, 2012 · read from New Brunswick Acts and Regulations on November 16, 2026
The text
(1) Subject to subsection (6), the owner or operator of an underground storage tank at a service station or marina shall measure the liquid level in the storage tank at least once each day the service station or marina is open in conformance with subsections (5) and (7) by a method acceptable to the Minister.
(2) Subject to subsection (6), the owner or operator of an underground storage tank at a service station or marina shall measure the level of water at the bottom of the underground storage tank at least once each day the service station or marina is open in conformance with subsections (5) and (7) by a method acceptable to the Minister.
(3) Subject to subsections (1) and (6), the owner or operator of a storage tank, except a storage tank containing a petroleum product used solely for the purpose of heating a premises, shall measure the liquid level in the storage tank at least once each week in conformance with subsections (5) and (7) by a method acceptable to the Minister.
(4) Subject to subsections (1) and (6), the owner or operator of a storage tank, except a storage tank containing a petroleum product used solely for the purpose of heating a premises, shall measure the level of water at the bottom of the storage tank at least once each week in conformance with subsections (5) and (7) by a method acceptable to the Minister.
(5) The person taking the measurements referred to in subsection (1), (2), (3) or (4) shall immediately reconcile them with receipt and issue records and, where available, meter readings and shall record the findings on a form approved by the Minister.
(6) The owner or operator of a storage tank containing waste petroleum product shall measure the level of the waste petroleum product in the storage tank and the level of water at the bottom of the tank at the end of the last business day in each week and at the beginning of the first business day in each week by a method acceptable to the Minister and shall, on the first business day of each week, reconcile the readings taken that day with those taken on the last business day of the previous week and record the findings on a form approved by the Minister.
(7) Where a loss of liquid or a gain of water of five millimetres or greater is indicated by the reconciliation made under subsection (5) or (6) or where the level of water at the bottom of an underground storage tank exceeds fifty millimetres the owner or operator of the system shall immediately take corrective action in accordance with section 44.
(8) A record for each storage tank showing the measurements required under subsection (1), (2), (3), (4) or (6), the records required under subsections (5) and (6) and a record of the computation of any loss of liquid or gain of water shall be kept on a form approved by the Minister and shall be retained for a period of at least two years for immediate examination by the Minister.
(9) Where a dipstick is used in making the measurements under this section, it shall be marked in increments of no greater than ten millimetres.
(10) No person shall use an electronic or other storage tank liquid level gauge to make the measurements under this section unless the gauge is approved by the Minister before use.
Read the Petroleum Product Storage and Handling on the Province's website ↗
Made under Clean Environment Act, c. C-6.