Petroleum Product Storage and Handling, N.B. Reg. 87-97
Section 63
Cite as Petroleum Product Storage and Handling, N.B. Reg. 87-97, s. 63 · current to June 13, 2012 · read from New Brunswick Acts and Regulations on November 16, 2026
The text
(1) Pneumatic leakage tests may be performed only on a new underground storage tank that does not contain and has never contained a petroleum product, after installation but before backfilling.
(2) Where a pneumatic leakage test is performed under subsection (1), the tank shall be considered to be leaking when any pressure drop is detected within a period of two hours after steady temperature and tank deflection conditions have been established and the source of pressure has been removed.
(3) Pneumatic test pressures applied to a new underground storage tank shall be measured by an instrument calibrated in increments not greater than one kilopascal.
(4) The test pressure for a pneumatic leakage test shall be not less than thirty kilopascals and not more than thirty-five kilopascals above atmospheric pressure.
Read the Petroleum Product Storage and Handling on the Province's website ↗
Made under Clean Environment Act, c. C-6.