Municipal Wastewater Regulation, B.C. Reg. 87/2012
Section 87
Additional monitoring requirements
Cite as Municipal Wastewater Regulation, B.C. Reg. 87/2012, s. 87 · last amended October 27, 2025 · read from BC Laws on November 17, 2026
The text
(1) In respect of a discharge having a maximum daily flow of 500 m3/d or more, after 60 days of compliance with the quality limit,
(a) the discharger must conduct weekly presence or absence testing for coliform monitoring,
(b) if the presence of any coliform is detected, daily fecal coliform testing must be reinstated until the quality limit is in compliance, and
(c) for the purpose of paragraph (b), 7 tests must be conducted to demonstrate compliance before weekly presence or absence testing may be resumed.
(2) A discharger of class D municipal effluent must monitor 24-hour flow as follows:
(a) if the maximum daily flow is less than 50 m3/d, weekly;
(b) if the maximum daily flow is 50 m3/d or more but less than 500 m3d, twice each week, and
(c) if the maximum daily flow is 500 m3/d or more, daily.
(3) A discharger must submit data gathered under section 86 and this section to a director, if the maximum daily flow is
(a) less than 50 m3/d, twice each year, or
(b) 50 m3/d or more, quarterly.
Read the Municipal Wastewater Regulation on BC Laws ↗
Made under Environmental Management Act, SBC 2003, c. 53.