Municipal Wastewater Regulation, B.C. Reg. 87/2012
Section 86
Monitoring requirements for discharges to ground
Cite as Municipal Wastewater Regulation, B.C. Reg. 87/2012, s. 86 · last amended October 27, 2025 · read from BC Laws on November 17, 2026
The text
A discharger must monitor municipal effluent quality and quantity in accordance with section 87 [additional monitoring requirements] and Table 6, 7 or 8, as applicable, of this section.
Table 6 — Monitoring Requirements
If Maximum Daily Flow < 50 m3/d Class A Class B Class C flow frequency weekly weekly weekly CBOD5, TSS frequency and type monthly grab samples monthly grab samples quarterly grab samples fecal coliform frequency and type monthly grab samples monthly grab samples none turbidity frequency and type monthly grab samples none none nitrogen total, and nitrate (as N) frequency and type monthly grab samples none none
Table 7 — Monitoring Requirements
If Maximum Daily Flow ≥ 50 m3/d and < 500 m3/d Class A Class B Class C flow frequency twice / week twice / week twice / week CBOD5, TSS frequency and type twice / month grab samples twice / month grab samples monthly grab samples fecal coliform frequency and type weekly grab samples weekly grab samples none turbidity frequency and type weekly grab samples none none nitrogen total, and nitrate (as N) frequency and type twice / month grab samples none none
Table 8 — Monitoring Requirements
If Maximum Daily Flow ≥ 500 m3/d Class A Class B Class C flow frequency daily daily daily CBOD5, TSS frequency and type weekly composite samples weekly composite samples twice / month composite samples fecal coliform frequency and type daily composite samples daily grab samples none turbidity frequency and type daily composite samples none none nitrogen total, and nitrate (as N) frequency and type weekly composite samples none none
Read the Municipal Wastewater Regulation on BC Laws ↗
Made under Environmental Management Act, SBC 2003, c. 53.