Municipal Wastewater Regulation, B.C. Reg. 87/2012

Section 79

Reductions in drainage pipe length

Cite as Municipal Wastewater Regulation, B.C. Reg. 87/2012, s. 79 · last amended October 27, 2025 · read from BC Laws on November 17, 2026

The text

(1) Despite section 78 (1) [drainage pipe length requirements], a qualified professional may provide for a reduction in drainage pipe length to a maximum of 40% if both of the following requirements are met: (a) under section 74 (2) [calculating flow], a qualified professional uses the actual maximum daily flow to design the wastewater facility; (b) the drainfield discharges class A or B effluent. (2) In the circumstances set out in subsection (3), a qualified professional may design a drainfield with deeper, narrower trenches and reduce the drainage pipe length to a value equal to the product of (a) the pipe length required under section 78, and (b) a factor of 1/H0.5 or 0.8, whichever is greater, where H is the drainage trench depth below pipe invert in metres. (3) The circumstances for the purposes of subsection (2) are as follows: (a) percolation rates are less than 5 minutes per 25 mm; (b) the maximum daily flow is equal to or greater than 37 m3/d; (c) the depth to groundwater, including any groundwater mounding effect, is more than 1 m below the bottom of the drainage trench.
Read the Municipal Wastewater Regulation on BC Laws ↗

Made under Environmental Management Act, SBC 2003, c. 53.