Municipal Wastewater Regulation, B.C. Reg. 87/2012

Section 75

Municipal effluent quality requirements

Cite as Municipal Wastewater Regulation, B.C. Reg. 87/2012, s. 75 · last amended October 27, 2025 · read from BC Laws on November 17, 2026

The text

(1) A discharger of class A, B or C municipal effluent must meet the applicable municipal effluent quality requirements set out in this section and listed in Table 3. (2) The median coliform values for 7 consecutive daily tests and any single value test must be less than the value specified in Table 3. (3) Despite subsection (1), for class C lagoon systems, the maximum TSS level must not exceed 60 mg/L. (4) In respect of class A and B municipal effluent that is discharged to a drainfield, (a) filtration is required to prevent solids carrying over into the disposal field, and (b) monitoring controls must be maintained to signal an alarm when filtration begins to malfunction. Table 3 — Municipal Effluent Quality Requirements Requirement Class A Class B Class C CBOD5 (mg/L) 10 10 45 TSS (mg/L) 10 10 45 fecal coliform (MPN / 100 mL) median: 2.2 any sample: 14 400, if maximum daily flow is ≥ 37 m3/d n/a turbidity (NTU) average: 2 any sample: 5 n/a n/a nitrogen (mg/L) Nitrate-N: 10 total N: 20 n/a n/a
Read the Municipal Wastewater Regulation on BC Laws ↗

Made under Environmental Management Act, SBC 2003, c. 53.