Occupational Health and Safety Regulation, B.C. Reg. 296/97

Section 9.21

Double block and bleed

Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, s. 9.21 · last amended September 1, 2027 · read from BC Laws on November 17, 2026

The text

If a double block and bleed isolation system is used (a) the diameter of the bleed line must be no less than the diameter of the line being isolated, unless certified by a professional engineer, (b) the bleed for a liquid system must be at a lower elevation than the block valves, (c) all valves must be locked out in their proper open or closed position, (d) the downstream block valve must be checked to ensure that it is capable of safely withstanding the line pressure, (e) the bleed must be checked to ensure that it remains clear of obstructions while the confined space is occupied, either by continuous automatic monitoring or by manually checking within 20 minutes before worker entry, or before re-entry after the confined space has been vacated for more than 20 minutes, and (f) in the event of discharge from the bleed line resulting from failure of the upstream block valve, all workers must immediately exit the confined space and the space must be effectively re-isolated before a worker enters the space.
Read the Occupational Health and Safety Regulation on BC Laws ↗

Made under Workers Compensation Act, RSBC 2019, c. 1.