Occupational Health and Safety Regulation, B.C. Reg. 296/97
Section 5.30
Dispensing
Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, s. 5.30 · last amended September 1, 2027 · read from BC Laws on November 17, 2026
The text
If a flammable liquid is dispensed or transferred inside a flammable liquids storage room,
(a) the storage room must be mechanically ventilated at a rate of at least 18 m3/hr per square metre of floor area (1 cfm/sq ft), but not less than 250 m3/hr (150 cfm),
(b) exhaust air must be discharged to the outdoors, and makeup air provided,
(c) any makeup air duct passing through a fire separation must be equipped with an approved fire damper, and
(d) doors must be self-closing.
Read the Occupational Health and Safety Regulation on BC Laws ↗
Made under Workers Compensation Act, RSBC 2019, c. 1.