Occupational Health and Safety Regulation, B.C. Reg. 296/97
Section 5.29
Electrostatic charge
Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, s. 5.29 · last amended September 1, 2027 · read from BC Laws on November 17, 2026
The text
If glass, plastic or other non-conductive container with a capacity of 23 litres (5 imp gal) or more is used to transfer a flammable liquid, the accumulation of electrostatic charge near the surface of the liquid must be eliminated or controlled by
(a) limiting the flow velocity of the liquid to less than 1 m/s (200 fpm),
(b) using a grounded lance or nozzle extending to the bottom of the container,
(c) limiting free fall,
(d) using anti-static additives, or
(e) other effective means.
Read the Occupational Health and Safety Regulation on BC Laws ↗
Made under Workers Compensation Act, RSBC 2019, c. 1.