Occupational Health and Safety Regulation, B.C. Reg. 296/97

Section 30.10

Ducting

Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, s. 30.10 · last amended September 1, 2027 · read from BC Laws on November 17, 2026

The text

(1) Laboratory fume hoods located in the same room or separate rooms may be connected to a common exhaust duct or manifold system if the following conditions are satisfied: (a) the requirements of section 5.3.2 of ANSI/AIHA Standard Z9.5-2003, Laboratory Ventilation are met; (b) controls to prevent backdrafts and pressure imbalances between rooms are installed; (c) the ventilation design and installation of the common exhaust duct or manifold system is certified by a professional engineer. (2) Despite subsection (1), laboratory fume hoods that are or will be used for working with (a) radioactive materials in amounts that exceed the exemption quantity specified by the Canadian Nuclear Safety Commission, or (b) perchloric acid must not be connected to a manifold system. (3) Ducting used in the installation of a laboratory fume hood must be designed in accordance with established engineering principles.
Read the Occupational Health and Safety Regulation on BC Laws ↗

Made under Workers Compensation Act, RSBC 2019, c. 1.