Occupational Health and Safety Regulation, B.C. Reg. 296/97
Section 23.10
Fire extinguishers
Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, s. 23.10 · last amended September 1, 2027 · read from BC Laws on November 17, 2026
The text
(1) Non-freezing fire extinguishers, other firefighting equipment and firefighting personnel must be provided as required by subsections (2), (3) and (4) and Table 23-1.
(2) The minimum requirements for a twin agent unit are
(a) 1 100 litres (250 imp gal) pre-mixed ATC foam solution at 6%,
(b) 680 kg (1 500 lbs) potassium bicarbonate dry chemical system,
(c) 30 m (100 ft) discharge hose, and
(d) two firefighting personnel.
(3) The minimum requirements for a continuous foam unit are
(a) 475 litres (100 imp gal) ATC foam concentrate,
(b) 680 kg (1 500 lbs) potassium bicarbonate dry chemical system,
(c) 1 900 litres (400 imp gal) per minute centrifugal certified fire pump with one 65 mm (2.5 in) discharge port, two 38 mm (1.5 in) discharge ports, and one 125 mm (5 in) suction port, and
(d) two firefighting personnel.
(4) Firefighting equipment must meet the requirements of NFPA 10, Portable Fire Extinguishers, 1990 Edition.