Occupational Health and Safety Regulation, B.C. Reg. 296/97
Section 19.34
Limits of approach
Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, s. 19.34 · last amended September 1, 2027 · read from BC Laws on November 17, 2026
The text
(1) Subject to section 19.34.1, a certified utility arborist and any conductive tool must not be closer to an energized high voltage conductor than the applicable limit of approach in column B of Table 19-3.
(2) An apprentice utility arborist, except as provided in subsection (3), and any tool being used must not be closer to an energized high voltage conductor than the applicable limit of approach in column C of Table 19-3, or to any vegetation that is closer than the column C limit or that could swing closer while being cut.
(3) An apprentice utility arborist may work up to the limit of approach permitted for a certified utility arborist in subsections (1) and (5) if the apprentice utility arborist is in the presence of and under the direct supervision of a certified utility arborist.
(4) Vegetation closer to an energized high voltage conductor than the applicable limit in column B of Table 19-3 must be cut using approved insulated tools.
(5) An insulated tool acceptable to the Board may be used by a certified utility arborist
(a) up to the limit of approach in column A of Table 19-3, and
(b) from an insulated aerial device to remove vegetation closer than the limit of approach in column A of Table 19-3 up to but not touching an energized high voltage conductor of 75 kV or less.
(6) Vegetation touching an energized high voltage conductor or within the applicable limit in column A of Table 19-3 for a conductor at a potential of 75 kV or more may be removed only if
(a) the line is isolated and grounded by a qualified electrical worker, or
(b) the vegetation is removed by a qualified electrical worker who
(i) is authorized by the owner of the power system to remove the vegetation, and
(ii) uses insulated tools and work methods approved under the authorization referred to in subparagraph (i).
(7) Vegetation encroaching past the limits of approach in column B of Table 19-3 that cannot be removed using an insulated aerial device must be restrained from encroaching past the limit of approach in column A before removal.
(8) A tree must be topped before being felled, or other precautions must be taken to prevent the tree or any part of it from falling closer than the limit of approach in column A of Table 19-3. Table 19-3: Limits of approach for utility arborists Voltage range A. Insulated tool limit
for certified utility
arborists B. Work limit for
certified utility
arborists C. Work limit for
apprentice utility
arborists Phase to phase Metres Feet Metres Feet Metres Feet Over 750 V to 20 kV 0.3 1 0.9 3 3 10 Over 20 kV to 30 kV 0.5 1.5 1.2 4 3 10 Over 30 kV to 75 kV 0.9 3 1.5 5 3 10 Over 75 kV to 250 kV 2.1 7 3 10 4.5 15 Over 250 kV to 325 kV 2.6 8.5 4.5 15 6 20 Over 325 kV to 550 kV 3.7 12 6 20 6 20
Read the Occupational Health and Safety Regulation on BC Laws ↗
Made under Workers Compensation Act, RSBC 2019, c. 1.