Occupational Health and Safety Regulation, B.C. Reg. 296/97

Section 19.27

Specially trained

Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, s. 19.27 · last amended September 1, 2027 · read from BC Laws on November 17, 2026

The text

(1) A worker who has taken a course of instruction approved by the Board may work up to the adjusted limits of approach in Table 19-2 when all the following conditions apply: (a) the high voltage electrical equipment is energized to a potential of not more than 75 kV; (b) the Board has determined that rerouting, de-energizing or guarding of the equipment is not practicable for the type of work being performed; (c) the work is not being done for the owner of the power system; (d) the work is of a type that must be done regularly; (e) the worker follows written safe work procedures acceptable to the Board. (2) A qualified electrical worker may work closer than the limits specified in Table 19-2 provided the worker is authorized by the owner of the power system and uses procedures acceptable to the Board. Table 19-2: Adjusted limits of approach Voltage Minimum distance Phase to phase Metres Feet Over 750 V to 20 kV 0.9 3 Over 20 kV to 30 kV 1.2 4 Over 30 kV to 75 kV 1.5 5
Read the Occupational Health and Safety Regulation on BC Laws ↗

Made under Workers Compensation Act, RSBC 2019, c. 1.