Occupational Health and Safety Regulation, B.C. Reg. 296/97

Section 19.26

Assurance not practicable

Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, s. 19.26 · last amended September 1, 2027 · read from BC Laws on November 17, 2026

The text

(1) If exposed high voltage electrical equipment and conductors cannot be isolated, rerouted or guarded, work must not be done within the minimum distance in Table 19-1A until the following precautions are taken: (a) the area within which equipment or materials are to be moved must be barricaded and supervised to restrict entry only to those workers necessarily engaged in the work; (b) a safety watcher must be designated; (c) a positive means must be provided for the safety watcher to give a clear, understandable stop signal to workers in the area, and the watcher must give the stop signal by no other means. (2) While equipment is in motion in an area in proximity to energized electrical equipment or conductors, no person other than the equipment operator may touch any part of the equipment or the material being moved by it. (3) No person may move a load or any rigging line from its position of natural suspension if it is in proximity to an energized electrical conductor or equipment.
Read the Occupational Health and Safety Regulation on BC Laws ↗

Made under Workers Compensation Act, RSBC 2019, c. 1.