Occupational Health and Safety Regulation, B.C. Reg. 296/97

Section 19.24.2

Minimum clearance distance when passing under exposed electrical equipment and conductors

Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, s. 19.24.2 · last amended September 1, 2027 · read from BC Laws on November 17, 2026

The text

(1) This section applies in the circumstance where a person working at a workplace is moving or is involved in moving equipment under exposed electrical equipment or conductors and is not performing any work other than work related to moving the equipment. (2) Unless otherwise permitted by this Part, in the circumstances set out in subsection (1), if exposed electrical equipment or conductors have a voltage within a range set out in column 1 of Table 19-1B, the following must maintain at least the clearance distance from the exposed electrical equipment and conductors that is set out in column 2 opposite that range of voltage: (a) a person moving or involved in moving the equipment under the exposed electrical equipment or conductor; (b) the equipment that a person referred to in paragraph (a) is moving; (c) the load carried by the equipment referred to in paragraph (b). Table 19-1B Column 1 Voltage Column 2 Minimum clearance distance when passing under exposed electrical equipment or conductors Phase to phase Metres Feet Over 750 V to 75 kV 2 6.5 Over 75 kV to 250 kV 3 10 Over 250 kV to 550 kV 4 13
Read the Occupational Health and Safety Regulation on BC Laws ↗

Made under Workers Compensation Act, RSBC 2019, c. 1.