Occupational Health and Safety Regulation, B.C. Reg. 296/97

Section 12.174

Pressure relief device — installation

Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, s. 12.174 · last amended September 1, 2027 · read from BC Laws on November 17, 2026

The text

(1) In this section “pressure relief device” means a pressure relief device referred to in section 12.173. (2) A pressure relief device must (a) have a flow capacity that is not less than the flow capacity of the pressure source, and (b) be set to discharge at not more than the pressure rating of the component in the pressurized system with the lowest pressure rating. (3) Any fluid or material discharged through a pressure relief device must be piped to a place where it will not endanger workers. (4) The diameter of piping connected to the pressure side and the discharge side of a pressure relief device must not be smaller than the diameter of the openings to the device. (5) The piping on the discharge side of a pressure relief device must be (a) secured to prevent movement, and (b) sloped to drain fluids away from the pressure relief device if freezing could restrict the fluid flow. (6) A valve must not be installed in the discharge opening of a pressure relief device, or the device's discharge pipe, unless required by engineering design. (7) A pressure relief device that requires block valves by engineering design must have the block valves locked in the appropriate position. (8) A guard must be installed around the shear pin and spindle of a pressure relief device.
Read the Occupational Health and Safety Regulation on BC Laws ↗

Made under Workers Compensation Act, RSBC 2019, c. 1.