Gasoline Vapour Control Regulation, B.C. Reg. 226/95

Section 6

Terminal requirements

Cite as Gasoline Vapour Control Regulation, B.C. Reg. 226/95, s. 6 · last amended October 28, 2019 · read from BC Laws on November 17, 2026

The text

(1) Effective May 1, 1996, every owner of (a) an existing terminal in the Lower Fraser Valley, or (b) a new terminal in the Lower Fraser Valley that in any calendar year transfers more than 250 million litres of gasoline to cargo tankers must equip the terminal with a vapour recovery system. (2) Effective May 1, 1996, every owner of a new terminal in the Lower Fraser Valley that in any calendar year transfers more than 25 million litres but less than 250 million litres of gasoline to cargo tankers must equip the terminal with a vapour recovery system or, if approved by a director, a vapour destruction system. (3) Effective May 1, 1996, the owner of a terminal required by this regulation to have a vapour recovery system or vapour destruction system must not permit the loading of gasoline from the terminal to a cargo tanker with a capacity of over 21 000 litres unless the cargo tanker is equipped with a vapour balancing system. (4) Effective May 1, 1996, every owner of a terminal required by this regulation to have a vapour recovery system or vapour destruction system must, at least once in every 12 months, (a) conduct tests specified in the CGSB Standard to ensure that vapour recovery unit or vapour destruction unit emissions do not exceed the level specified by the CGSB Standard, and (b) test the vapour control system for leaks. (5) Every vapour recovery system or vapour destruction system must (a) use vapour connections for cargo tanker hook-ups designed to prevent the release of vapour to the atmosphere, (b) include collection systems for condensate, and (c) have a minimum of 2 vapour connections at each loading bay capable of loading 2 or more cargo tankers simultaneously. (6) Except as provided by subsection (7), the owner of a terminal required to be equipped with a vapour recovery system or vapour destruction system must ensure that (a) the facility has an operating service factor in each calendar year of 95% or greater, and (b) planned maintenance involving reductions in the effectiveness of vapour control does not occur between May 1 and September 15 of each year. (7) A terminal may have an operating service factor of less than 95% during a calendar year if (a) a director finds that the terminal owner has used due diligence in keeping the terminal's vapour recovery system or vapour destruction system operative, and (b) the terminal complies with a plan approved by the director to bring the terminal into compliance with subsection (6). (8) The owner of a terminal required to have a vapour recovery system or vapour destruction system must notify a director if the system is inoperative or is expected to be inoperative for a period exceeding 48 hours. (9) Every owner of a terminal that is required to have a vapour recovery system or vapour destruction system must ensure the proper operation of the system and, without restricting the foregoing, must do all of the following: (a) provide adequate training to employees operating the system; (b) provide written operating procedures to cargo tank operators and employees operating the system; (c) provide written standard maintenance procedures to employees maintaining the system; (d) conduct periodic visual checks of the system to ensure that it is in good working order.
Read the Gasoline Vapour Control Regulation on BC Laws ↗

Made under Environmental Management Act, SBC 2003, c. 53.