Gasoline Vapour Control Regulation, B.C. Reg. 226/95

Section 5

Bulk plant requirements

Cite as Gasoline Vapour Control Regulation, B.C. Reg. 226/95, s. 5 · last amended October 28, 2019 · read from BC Laws on November 17, 2026

The text

(1) Effective May 1, 1996, every owner of a bulk plant in the Lower Fraser Valley that (a) commences operations after September 1, 1995 and in any calendar year receives 4.5 million litres or more of gasoline, (b) expands capacity after September 1, 1995 and in any calendar year after expansion receives 4.5 million litres or more of gasoline above that which the bulk plant received on average in the 3 calendar years before the expansion, or (c) has received 20 million litres or more of gasoline in any calendar year after 1991 must equip each gasoline vapour storage tank with vapour balancing systems both for unloading from a cargo tanker and for delivery to a cargo tanker. (2) Effective May 1, 1996, every owner of a bulk plant in the Lower Fraser Valley that has received 4.5 million litres or more of gasoline in any calendar year after 1991 must equip each gasoline storage tank with a vapour balancing system for unloading from a cargo tanker to the storage tank. (3) Subsections (1) and (2) do not apply to unloading from a cargo tanker if the gasoline storage tank is equipped with a floating roof tank. (4) Effective May 1, 1996, every owner of a bulk plant in the Lower Fraser Valley that is required to have a vapour balancing system must, at least once in every 24 months, test the system for leaks. (5) Vapour balancing systems required by this section must (a) use vapour connections for cargo tanker hook-ups designed to prevent the release of vapour into the atmosphere, and (b) include collection systems for condensate. (6) Every owner of a bulk plant that is required to have a vapour control system must ensure the proper operation of the system and, without restricting the foregoing, must (a) provide adequate training to employees operating the system, (b) provide written operating procedures to cargo tank operators and employees operating the system, and (c) conduct periodic visual checks of the vapour balancing system to ensure that it is in good working order.
Read the Gasoline Vapour Control Regulation on BC Laws ↗

Made under Environmental Management Act, SBC 2003, c. 53.