Gasoline Vapour Control Regulation, B.C. Reg. 226/95

Section 7

General requirements

Cite as Gasoline Vapour Control Regulation, B.C. Reg. 226/95, s. 7 · last amended October 28, 2019 · read from BC Laws on November 17, 2026

The text

(1) Effective May 1, 1996, a person must not transfer more than 500 litres of gasoline between a facility equipped with a vapour control system and a cargo tanker equipped with vapour balancing system unless the systems have been properly connected prior to the transfer. (2) Effective May 1, 1996, a person must not transfer more than 500 litres of gasoline from a bulk plant or terminal to a cargo tanker unless (a) the transfer is carried out by submerged fill, or (b) the transfer is carried out between a facility and a cargo tanker, both of which are equipped with and use vapour control systems. (3) The owner of a facility or cargo tanker that is required to have a vapour control system must, except where otherwise provided by this regulation, ensure that the system complies with the CGSB Standard and is installed, operated and maintained in accordance with the recommendations and requirements of the CGSB Standard. (4) Leak testing of terminals and bulk plants, as required by this regulation, must be conducted using a combustible gas meter and must be tested as specified in the CGSB Standard while the vapour control system is in use.