Power Engineers, Boiler, Pressure Vessel and Refrigeration Safety Regulation, B.C. Reg. 104/2004
Section 3
Application of this regulation
Cite as Power Engineers, Boiler, Pressure Vessel and Refrigeration Safety Regulation, B.C. Reg. 104/2004, s. 3 · last amended December 31, 2024 · read from BC Laws on November 17, 2026
The text
(1) This regulation applies in respect of every boiler and boiler plant, every pressure plant, every pressure vessel, every pressure piping system, every fitting, every plant and all refrigeration equipment and refrigeration plants.
(2) Despite subsection (1), this regulation does not apply to any of the following:
(a) a power plant with a heating surface of 2 m2 or less;
(b) a heating plant with a heating surface of 3 m2 or less;
(c) Repealed. [B.C. Reg. 134/2009, s. 11 (a).]
(d) a low pressure thermal fluid plant with a heating surface of 3 m2 or less;
(e) a heating plant that has no valves or other obstruction to prevent circulation of fluid between the boiler and an expansion tank that is fully vented to the atmosphere;
(f) a heating plant, refrigeration plant or pressure vessel plant, other than plants with toxic or flammable contents, that is located in a building that contains only 4 or fewer self-contained residential units;
(g) a pressure vessel operating at and with relief valves set at a pressure of 103 kPa or less;
(h) a pressure vessel not equipped with heating element that is constructed for the storage of water at a temperature of 65C or less and a pressure of 1 720 kPa or less or has a diameter of 610 mm or less;
(i) a pressure vessel used for hydraulic purposes having an operating temperature of less than 82C, if the primary design considerations are mechanical in nature and stresses are derived from the functional requirements of the device rather than fluid pressure;
(j) a refrigeration plant with a capacity of less than 5 kW prime mover nameplate rating;
(k) a cushion tank with a diameter of 610 mm or less that is constructed to operate at a working pressure of 207 kPa or less;
(l) a distribution main or service pipe as defined in the Gas Safety Regulation;
(m) piping and fittings external to the boiler proper in a low temperature, low pressure fluid plant or a heating plant;
(n) a pressure piping system operating at and with a relief valve or valves set at 103 kPa or less;
(o) a water heater with a heat input of 120 kW or less;
(p) a boiler or pressure vessel subject to the jurisdiction of Transport Canada under the Transportation of Dangerous Goods Act (Canada) or a boiler or pressure vessel subject to the Canadian Shipping Act;
(q) gas-insulated switchgear and control gear used for control of high voltage electricity;
(r) refrigeration equipment used for air conditioning or refrigerated compartments on railway cars, motor vehicles, motor-drawn vehicles, aircraft or ships;
(s) air or hydraulic brake systems subject to the Motor Vehicle Safety Regulations under the Motor Vehicle Safety Act (Canada);
(t) air or hydraulic brake or steering systems for off road vehicles;
(u) penstocks;
(v) domestic water piping systems used in buildings or other structures;
(w) medical gas piping systems.
(3) Repealed. [B.C. Reg. 104/2004, s. 3 (4).]
(4) Subsection (3) is repealed on April 1, 2014.
Read the Power Engineers, Boiler, Pressure Vessel and Refrigeration Safety Regulation on BC Laws ↗
Made under Safety Standards Act, SBC 2003, c. 39.