Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations, SOR/2025-88
Section 96
Inspection every five years
Cite as Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations, SOR/2025-88, s. 96 · current to July 24, 2025 · regulation last amended July 5, 2025
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
The operator of a facility must ensure that each external floating roof at the facility and the exposed part of the internal wall of the tank in which it is installed are inspected every five years and that the inspection includes
(a) a measurement of the primary seal gaps under the control conditions and in accordance with the procedure described in Schedule 4, unless the rim seal is being replaced at the time of the inspection;
(b) an inspection of the primary and secondary seals in which they are pulled back all around the internal wall and checked for their proper operation;
(c) an inspection of the secondary seals for signs of buckling or indications that the angle with the internal wall is too shallow;
(d) an inspection of all hatches, covers and other emissions control devices, including seals and internal floats, to locate tears, holes, corrosion, swelling, embrittlement or any other damage that would substantially reduce their emissions control efficacy;
(e) an inspection of the exposed part of internal wall of the tank for grooving, corrosion, coating failures and out-of-roundness;
(f) if applicable, an inspection of the automatic gauging guide of the tank and the lower sheave housing for signs of vapour leaks and liquid leaks;
(g) an inspection of the wind girder for corrosion damage;
(h) a visual inspection of the external floating roof for inadequate drainage;
(i) if applicable, a test operation of the hatches to verify that they seal automatically after use;
(j) if applicable, an inspection of all guide poles and gauge wells for thinning and signs of grooving or wear;
(k) an inspection of the levelness of the external floating roof, at a minimum of three locations, in which the distance from the roof rim to a horizontal weld seam that is above the floating roof is measured;
(l) an inspection of the emergency drains to ensure that the covers or sealing are adequate;
(m) if applicable, an inspection of the inside the pontoons and a determination of the value of the LEL% inside of the pontoons to detect vapour leaks and liquid leaks;
(n) an inspection of the upper deck of the external floating roof for paint failure and corrosion; and
(o) if applicable, an inspection of the bolting bar on the rim-mounted secondary seals for corrosion and broken welds.
Read the Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations on the Justice Laws Website ↗
Made under Canadian Environmental Protection Act, 1999, S.C. 1999, c. 33.