Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations, SOR/2025-88
Section 88
Performance test — modifications
Cite as Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations, SOR/2025-88, s. 88 · current to July 24, 2025 · regulation last amended July 5, 2025
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) If the vapour control system is a vapour recovery system or vapour destruction system, the operator must ensure that the performance test referred to in section 87 is performed in accordance with section 7 of the National Standard of Canada CAN/CGSB 3.1000–2024, entitled Vapour Control Systems in Gasoline Distribution Networks, with the following modifications:
(a) the test method applies to all vapour recovery systems and vapour destruction systems;
(b) a reference to “terminal” is to be read as a reference to “facility”;
(c) a reference to “gasoline” is to be read as a reference to “volatile petroleum liquid”;
(d) a reference to “gasoline vapour” is to be read as a reference to “ vapour”;
(e) if the vapour control system is used to control VOC emissions from a tank, the performance test period must be of the same duration as the performance test period set out in the standard and include at least one hour during which the tank is being filled at the maximum rate;
(f) the use of alternate test methods, including continuous emissions monitoring, is not permitted;
(g) the total hydrocarbon analyzer must be a separate device from the continuous monitoring device and both devices must independently collect data throughout the test period;
(h) detections of methane and ethane may be excluded from the results collected by the total hydrocarbon analyzer by either
(i) using a device of a type that is insensitive to those substances, or
(ii) subtracting the effect of those substances from the reading using a calibration or correction factor that is established on the day of the test and appropriate for the testing conditions, including temperature, pressure, overall atmospheric composition and actual vapour composition;
(i) in all calculations and calibrations, references to propane or the properties of propane, including density or molecular mass, must be replaced by references to another appropriate substance or to the properties of that other substance whenever necessary to accurately represent the properties of a volatile petroleum liquid;
(j) the volume of substances that are not volatile petroleum liquids must not be included in calculations relating to the volume of liquid loaded; and
(k) the results of the calculations may indicate the performance of the vapour control system in terms of the mass of VOCs emitted per m3 of vapour vented instead of the mass of VOCs emitted per litre of liquid loaded.
(2) For the purposes of paragraph (1)(e), if the vapour control system is used to control the emissions of multiple tanks, only one tank must be filled during the test.
(3) The accuracy of a continuous monitoring device referred to in paragraph 54(1)(a) is evaluated by comparing the measurements generated by the device during the test to the results of the performance test referred to in section 87.
Read the Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations on the Justice Laws Website ↗
Made under Canadian Environmental Protection Act, 1999, S.C. 1999, c. 33.