Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations, SOR/2025-88
Section 74
Gap between seal and wall of tank
Cite as Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations, SOR/2025-88, s. 74 · current to July 24, 2025 · regulation last amended July 5, 2025
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) Any space that is between the rim seal of the external floating roof and the wall of the tank is considered to be a seal gap, which must be measured under the control conditions and in accordance with the procedure described in Schedule 4.
(2) Subject to subsection (3), the operator must ensure that the seal gaps in each seal are less than the following dimensions:
(a) if the seal is the primary seal,
(i) 4 cm wide at every point between the seal and the wall of the tank, and
(ii) a cumulative total of 200 cm2 per metre of the tank’s diameter; and
(b) if the seal is a secondary seal,
(i) 1.3 cm wide at every point between the seal and the wall of the tank, and
(ii) a cumulative total of 20 cm2 per metre of the tank’s diameter.
(3) If the external floating roof is equipped with more than one secondary seal, the operator must ensure that at least one of the secondary seals meets the size requirements set out in subparagraphs (2)(b)(i) and (ii).
Read the Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations on the Justice Laws Website ↗
Made under Canadian Environmental Protection Act, 1999, S.C. 1999, c. 33.
Bills in Parliament that would change this section 0
No bill we hold would amend or repeal this section.