Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations, SOR/2025-88
Section 73
Continuous vapour-tight enclosure
Cite as Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations, SOR/2025-88, s. 73 · current to July 24, 2025 · regulation last amended July 5, 2025
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) The operator must ensure that each external floating roof is equipped with a primary seal and a secondary seal that form a continuous vapour-tight enclosure around the entire perimeter of the floating roof, except where the seals are in contact with the tank wall, in which case the seal gaps must meet the requirements set out in subsection 74(2).
(2) The operator must ensure that each primary seal is of one of the following types:
(a) a foam seal or liquid-filled seal that rests in continuous contact with the surface of the liquid; or
(b) a mechanical shoe seal composed of a curved metal sheet designed to be in continuous contact with the tank wall for a distance extending at least 60 cm above and 10 cm below the surface of the liquid.
(3) The operator must ensure that each secondary seal is of a type that is mounted on the rim of the external floating roof.
(4) A peripheral structure that covers a primary or secondary seal for the primary purpose of providing it shelter from rain, snow or ultraviolet radiation is not considered to be a secondary seal.
Read the Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations on the Justice Laws Website ↗
Made under Canadian Environmental Protection Act, 1999, S.C. 1999, c. 33.