Multi-Sector Air Pollutants Regulations, SOR/2016-151

Section 9

Transitional boilers and heaters

Cite as Multi-Sector Air Pollutants Regulations, SOR/2016-151, s. 9 · current to January 19, 2026 · regulation last amended January 1, 2026

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

The NOx emission intensity of a transitional boiler or heater that, for a given hour, has at least 50% of the input energy in its combustion chamber resulting from the introduction of gaseous fossil fuel must not, for that hour, exceed the following limit: (a) 26 g/GJ, if the boiler or heater has a rated capacity of at least 10.5 GJ/h and at most 105 GJ/h; and (b) subject to section 10, 40 g/GJ, if the boiler or heater has a rated capacity greater than 105 GJ/h.
Read the Multi-Sector Air Pollutants Regulations on the Justice Laws Website ↗

Made under Canadian Environmental Protection Act, 1999, S.C. 1999, c. 33.

Bills in Parliament that would change this section 0

No bill we hold would amend or repeal this section.