Redesigned boilers and heaters — NOx emission intensity
Cite as Multi-Sector Air Pollutants Regulations, SOR/2016-151, s. 10 · current to January 19, 2026 · regulation last amended January 1, 2026
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) The NOx emission intensity of a redesigned boiler or heater that, for a given hour, has at least 50% of the input energy in its combustion chamber resulting from the introduction of gaseous fossil fuel must not, for that hour, exceed the limit of 26 g/GJ.
(2) A redesigned boiler or heater is one that
(a) on its commissioning date, was not designed to combust gaseous fossil fuel; and
(b) after the day on which these Regulations are registered, is redesigned to combust, on its recommissioning date, gaseous fossil fuel.
Read the Multi-Sector Air Pollutants Regulations on the Justice Laws Website ↗
Made under Canadian Environmental Protection Act, 1999, S.C. 1999, c. 33.