(1) Vapourizers, if housed, should be installed in detached buildings used exclusively for liquefied petroleum gas vapourization and if the vapourizer is installed in a lean-to, shed or room of a building, such building may only be used for liquefied petroleum gas operations. (2) The vapourizer building or room, as the case may be, shall be constructed of non-combustible or fire resistant materials, shall be cross-ventilated at the floor and ceiling levels by louvered openings, and should be provided with not less than 1 square foot of explosion relief venting on the open side per 40 cubic feet of inside space.