Vapourizers, heating devices for vapourizers, and vapourizers buildings shall be separated from loading and unloading sites, tanks, location on an adjoining property which may be built upon or other buildings by distances not less than the following:
(a) indirect fired vapourizers, 10 feet;
(b) heating devices for indirect fired vapourizers, 25 feet;
(c) direct fired vapourizers, with a capacity of 100 gallons per hour or less, 25 feet; and
(d) direct fired vapourizers with a capacity exceeding 100 gallons per hour, 50 feet.