The text

(1) A direct fired vapourizer or the heating device which supplies steam, hot water, or other fire-safe heating medium for an indirect fired vapourizer shall be separated from all other liquefied petroleum gas equipment, such as pumps or gas mixing devices by fireproof and vapourproof walls. Access to such vapourizer and heating device shall be from the outside only. The firewall shall be of not less than 1 hour fire resistance. Other parts of the room housing the heating device shall be constructed of noncombustible or fire resistant material. Cross ventilation shall be provided by other means than doors and windows. (2) This section does not apply to domestic water heaters which may supply heat for a vapourizer in a domestic system.
Read the Liquefied Petroleum Gases Bulk Storage Regulations on the Justice Laws Website ↗

Made under Railway Safety Act, R.S.C. 1985, c. 32 (4th Supp.).