A safety relief valve venting to the outside atmosphere shall be installed between each pair of shut-off valves on liquefied petroleum gas liquid lines where liquid may be trapped. The start to discharge pressure setting shall not be in excess of 5000 psig. The minimum setting shall not be lower than 140 per cent of the container relief valve setting, except that for 1.C.C. or B.T.C. containers, the minimum setting shall not be lower than 400 psig.