Liquefied Petroleum Gases Bulk Storage Regulations, C.R.C., c. 1152
Section 54
Cite as Liquefied Petroleum Gases Bulk Storage Regulations, C.R.C., c. 1152, s. 54 · current to July 24, 2025 · regulation last amended June 18, 2015
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) For tanks exceeding 2,000 Imperial gallons water capacity, the discharge from tank safety relief devices shall be vented vertically to the outside atmosphere at a point not less than 7 feet above the storage tank. Such discharge should be at least 100 feet and in no case shall it be less than 50 feet from any open flame or source of ignition.
(2) For tanks with a water capacity of 2,000 Imperial gallons or less, the discharge from safety relief devices shall be vented vertically to the outside atmosphere in a manner that will prevent the gases from impinging on the tank.
(3) The ends of relief valve discharge pipes shall be fitted with loose rain caps that cannot freeze in place.
(4) All storage tank relief devices shall be located on the storage tank and shall have direct communication with the vapour space of the storage tank.
(5) If the design of the safety relief system is such that liquid can collect on the discharge side of the disc, provision shall be made for drainage of the liquid.
(6) Return bends and restrictive pipe fittings are not permitted in relief valve piping.
(7) Safety relief devices shall be so arranged that the possibility of tampering will be minimized.
(8) External pressure settings or adjustments shall be sealed.
Read the Liquefied Petroleum Gases Bulk Storage Regulations on the Justice Laws Website ↗
Made under Railway Safety Act, R.S.C. 1985, c. 32 (4th Supp.).