(1) Every storage tank and vapourizer (except as provided in Part VII) shall be provided with one or more safety relief valves of the spring loaded type or an equivalent type which have been approved for the intended service by the Boiler and Pressure Vessel Committee of the A.S.M.E. or the Compressed Gas Association, Inc. or Underwriters’ Laboratories.
(2) Such valves shall be of a size that will ensure a rate of discharge not less than specified in the current edition of National Fire Protection Association’s Pamphlet No. 58.
(3) The rate of discharge prescribed in subsection (2) shall be obtained before the pressure is in excess of 120 per cent of the maximum (not including the permitted plus tolerance of 10 per cent) permitted start to discharge pressure setting of the device.
(4) Safety relief valves shall be installed in a manner that will ensure that the full relief requirements are always satisfied.
(5) Storage tank and vapourizer safety relief valves shall be set to start to discharge at pressures as prescribed in the current edition of the National Fire Protection Association’s Pamphlet No. 58 for vessels designed according to the A.S.M.E. Code.