HEALTH CARE AND RESIDENTIAL FACILITIES, O. Reg. 67/93

Section 74

Cite as HEALTH CARE AND RESIDENTIAL FACILITIES, O. Reg. 67/93, s. 74 · current to November 11, 2026 · consolidated from June 9, 2025 · read from e-Laws on November 16, 2026

The text

(1) A storage cylinder for compressed gas shall, (a) have a valve connection which prevents an inadvertent connection that would result in a hazardous mixture of gases; (b) be secured in position during transportation, storage or use; (c) not be rolled, slid or dropped; (d) if designed for the use of a valve protection cap, have the valve protection cap in position when the cylinder is being transported or stored; (e) if it contains acetylene, be in an upright position; (f) be protected from physical damage; (g) if it is empty, be labelled accordingly and have the valve securely turned off; and (h) be stored in a well-ventilated area, away from any source of ignition. (2) Subsection (1) does not apply to fire extinguishers or calibration equipment. (3) A cylinder containing compressed flammable gas shall be stored, (a) at least six metres from any cylinder containing oxygen; or (b) with a barrier of noncombustible material at least 1.5 metres high having a fire resistance rating of at least one-half hour separating it from any cylinder containing oxygen. (4) The area where compressed gas cylinders are stored shall be posted as a no smoking area and no person shall smoke in the area. O. Reg. 67/93, s. 74.
Read the HEALTH CARE AND RESIDENTIAL FACILITIES on e-Laws ↗

Made under Occupational Health and Safety Act, R.S.O. 1990, c. O.1.