CONSTRUCTION PROJECTS, O. Reg. 213/91
Section 57
Cite as CONSTRUCTION PROJECTS, O. Reg. 213/91, s. 57 · current to November 11, 2026 · consolidated from April 20, 2026 · read from e-Laws on November 16, 2026
The text
(1) As construction proceeds in a building with two or more storeys, a permanent or temporary standpipe shall be installed such that the distance between the standpipe and the uppermost work level is no more than two storeys at any given time. O. Reg. 142/17, s. 10.
(2) Subsection (1) does not apply to work carried out in a building which is not required by the Building Code to have a permanent standpipe. O. Reg. 213/91, s. 57 (2).
(3) A permanent standpipe,
(a) shall have sufficient hose outlets to permit every part of the building to be protected by a hose not longer than twenty-three metres;
(b) shall have a connection for the use of the local fire department located on the street side of the building not more than 900 millimetres and not less than 300 millimetres above ground level and to which there is clear access at all times; and
(c) shall be maintained so as to be readily operable if required to be used. O. Reg. 213/91, s. 57 (3).
(4) Every hose outlet in a permanent standpipe shall have a valve. O. Reg. 213/91, s. 57 (4).
(5) Every hose used with a permanent standpipe,
(a) shall be at least thirty-eight millimetres in diameter;
(b) shall have a combination straight stream and fog nozzle; and
(c) shall be stored on a rack in such a way as to protect it from damage and keep it available for immediate use. O. Reg. 213/91, s. 57 (5).
(6) If a temporary standpipe has been installed, it shall not be disconnected until the permanent standpipe is connected, so that there is always a standpipe in service. O. Reg. 145/00, s. 18 (2).
(7) A temporary standpipe shall be maintained so that it is readily operable. O. Reg. 145/00, s. 18 (2).
(8) A temporary standpipe shall have at least one hose outlet per floor, with a valve and a hose attached to each hose outlet and a nozzle attached to each hose. O. Reg. 145/00, s. 18 (2).
(9) In addition to the requirements of subsection (8), there shall be a connection to which there is clear access at all times, located between 30 and 90 centimetres above ground level on a side of the building that faces the street. O. Reg. 145/00, s. 18 (2).
(10) A hose outlet on a temporary standpipe,
(a) shall have a valve; and
(b) shall be capable of accepting a hose that is 38 millimetres in diameter. O. Reg. 145/00, s. 18 (2).
(11) If a temporary standpipe is installed in a building under construction, the constructor shall post at the project, or have available for review, a floor plan of the building indicating,
(a) the location of the hose outlets on each floor;
(b) the location of the point on the perimeter of each floor that is furthest from the hose outlet on that floor; and
(c) the location of each exit on each floor. O. Reg. 145/00, s. 18 (2).
(12) The constructor shall give a copy of the floor plan to the fire department located nearest to the project. O. Reg. 145/00, s. 18 (2).
Read the CONSTRUCTION PROJECTS on e-Laws ↗
Made under Occupational Health and Safety Act, R.S.O. 1990, c. O.1.