CONSTRUCTION PROJECTS, O. Reg. 213/91

Section 56

Cite as CONSTRUCTION PROJECTS, O. Reg. 213/91, s. 56 · current to November 11, 2026 · consolidated from April 20, 2026 · read from e-Laws on November 16, 2026

The text

No work shall be carried out at a height of 84 metres or more in a building unless the building has temporary or permanent fire pumps that provide a minimum water flow of 1,890 litres per minute at a discharge pressure of at least 450 kilopascals at and above the 84-metre height. O. Reg. 145/00, s. 17.