CONSTRUCTION PROJECTS, O. Reg. 213/91

Section 194

Cite as CONSTRUCTION PROJECTS, O. Reg. 213/91, s. 194 · current to November 11, 2026 · consolidated from April 20, 2026 · read from e-Laws on November 16, 2026

The text

(1) A switch and panel board controlling a service entrance, service feeder or branch circuit shall meet the requirements of this section. O. Reg. 627/05, s. 7. (2) A switch and panel board shall be securely mounted on a soundly constructed vertical surface and shall have a cover over uninsulated parts carrying current. O. Reg. 627/05, s. 7. (3) A switch and panel board shall be located, (a) in an area where water will not accumulate; and (b) within easy reach of workers and readily accessible to them. O. Reg. 627/05, s. 7. (4) The area in front of a panel board shall be kept clear of obstructions. O. Reg. 627/05, s. 7. (5) A switch that controls a service entrance, service feeder or branch circuit providing temporary power, (a) shall not be locked in the energized position; and (b) shall be housed in an enclosure that can be locked and is provided with a locking device. O. Reg. 627/05, s. 7.