MINES AND MINING PLANTS, R.R.O. 1990, Reg. 854
Section 158
Cite as MINES AND MINING PLANTS, R.R.O. 1990, Reg. 854, s. 158 · current to November 11, 2026 · consolidated from July 1, 2025 · read from e-Laws on November 16, 2026
The text
(1) This section applies with respect to all work done on electrical equipment or conductors, other than work that is performed on energized equipment as permitted under subsection 159 (1). O. Reg. 265/15, s. 7.
(2) An employer shall establish a written locking and tagging program to protect the health and safety of workers. O. Reg. 265/15, s. 7.
(3) Before doing any work to which this section applies, a worker shall verify, by testing, that the following requirements have been complied with:
1. All hazardous sources of electrical supply to the electrical equipment or conductors are isolated.
2. Subject to subsection (4), all energy isolating devices are properly engaged, locked and tagged in accordance with subsection (5).
3. All hazardous stored electrical energy is discharged. O. Reg. 265/15, s. 7.
(4) A locking device required under paragraph 2 of subsection (3) may be omitted where,
(a) the locking device in itself creates a hazard due to the design of the energy isolating device; or
(b) circuit breakers or fuses for voltages of less than 150 volts to ground are not equipped with a means of locking. O. Reg. 265/15, s. 7.
(5) A tag required under paragraph 2 of subsection (3) shall,
(a) be secured to prevent its inadvertent removal;
(b) state the reason the energy isolating devices are locked and tagged;
(c) show the name of the person responsible for locking and tagging the energy isolating devices;
(d) show the date on which the energy isolating devices were locked and tagged;
(e) be made of nonconducting materials; and
(f) be installed so as not to become energized. O. Reg. 265/15, s. 7.