GENERAL, O. Reg. 246/22

Section 21

Lighting

Cite as GENERAL, O. Reg. 246/22, s. 21 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

Every licensee of a long-term care home shall ensure that the lighting is maintained in accordance with the following requirements: 1. In a home to which a design manual, other than a manual from earlier than 2009, was applicable under a development agreement to which the home was subject, i. all corridors and enclosed stairways shall have continuous consistent lighting throughout with minimum levels of 322.92 lux, and ii. all other areas of the home, including resident bedrooms and vestibules, washrooms and tub and shower rooms, shall have lighting with minimum levels of 322.92 lux. 2. In all other homes, i. all corridors shall have continuous consistent lighting throughout with minimum levels of 215.28 lux, ii. all stairways shall have continuous consistent lighting throughout with minimum levels of 322.92 lux, iii. the bed of each resident, when at the reading position, shall have lighting with minimum levels of 376.73 lux, iv. each drug cabinet shall have lighting with minimum levels of 1,076.39 lux, and v. all other areas of the home shall have lighting with minimum levels of 215.28 lux.
Read the GENERAL on e-Laws ↗

Made under Fixing Long-Term Care Act, 2021, S.O. 2021, c. 39, Sched. 1.