AIR POLLUTION — DISCHARGE OF SULPHUR DIOXIDE FROM PETROLEUM FACILITIES, O. Reg. 88/22

Section 16

Hydrogen sulphide in fuel gas

Cite as AIR POLLUTION — DISCHARGE OF SULPHUR DIOXIDE FROM PETROLEUM FACILITIES, O. Reg. 88/22, s. 16 · current to November 11, 2026 · consolidated from February 25, 2022 · read from e-Laws on November 16, 2026

The text

(1) A person shall not convey or cause or permit the conveyance of fuel gas to a flare, carbon monoxide boiler or general combustion device at a petroleum facility if the concentration of hydrogen sulphide in the fuel gas at a measurement point in respect of the flare, carbon monoxide boiler or general combustion device exceeds, (a) 162 parts per million by volume, averaged over any three-hour period; or (b) 60 parts per million by volume, averaged over any 365-day period. (2) Clause (1) (b) does not apply in respect of fuel gas conveyed to a flare. (3) Subsection (1) does not apply in respect of fuel gas conveyed to, (a) a carbon monoxide boiler, if the fuel gas is conveyed from the cracking unit with which the boiler is associated; or (b) a general combustion device, unless the approved continuous monitoring plan for the petroleum facility indicates that the concentration of hydrogen sulphide in the fuel gas conveyed to the general combustion device is to be measured.
Read the AIR POLLUTION — DISCHARGE OF SULPHUR DIOXIDE FROM PETROLEUM FACILITIES on e-Laws ↗

Made under Environmental Protection Act, R.S.O. 1990, c. E.19.