fire code, O. Reg. 213/07
Section 9.9.5.2
Cite as fire code, O. Reg. 213/07, s. 9.9.5.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) In buildings that are greater than 3 storeys in building height, a standpipe and hose system shall be installed in conformance with Subsection 3.2.9. of the 1994 Building Code.
(2) A standpipe and hose system installed in conformance with Sentences (3) to (6) is deemed to be in compliance with Sentence (1).
(3) Hose stations shall
(a) be located so that all areas
(i) are protected by a hose station on the same storey, and
(ii) can be reached by a hose stream and are within 6 m of a hose nozzle when the hose is extended,
(b) be provided with a 38 mm hose valve, unless otherwise approved,
(c) be equipped with not more than 30 m of 38 mm hose on a hose rack, unless otherwise approved,
(d) have the hose attached, ready for use at all times and equipped with a shut-off combination fog and straight stream nozzle,
(e) be within easy reach of a person standing on the floor, with the hose valve connection located no more than 1.5 m from the floor, and
(f) be located
(i) in corridors where possible, and
(ii) in hose cabinets.
(4) Despite Subclause (3)(a)(i), a penthouse may be protected by a hose station located in the storey below.
(5) A standpipe and hose system shall
(a) have an adequate water supply capable of producing a hose stream of at least 6 m from the hose nozzle at the highest fire hose outlet, and
(b) be served by at least one fire department connection located on the outside of the building adjacent to a street, readily accessible to the fire department.
(6) Hose cabinets shall be
(a) of sufficient size to accommodate a hose, hose rack, hose valve and portable extinguisher,
(b) conspicuously identified, by lettering at least 50 mm high or by the provision of a sufficiently large glass panel in the door to ensure that the equipment in the cabinet is readily visible,
(c) equipped with a door without locks, constructed to open easily, unless otherwise approved, and
(d) so located that the door, when open, will not obstruct any doorway.