fire code, O. Reg. 213/07

Section 9.9.4.1

Cite as fire code, O. Reg. 213/07, s. 9.9.4.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) A fire alarm system with listed components shall be installed in each building in accordance with Articles 9.9.4.2. to 9.9.4.12. where (a) the building area is more than 600 m2, (b) the building is more than 1 storey in building height, or (c) each guest suite is not served by an exterior exit facility leading to ground level. (2) A building is deemed to be in compliance with Sentence (1) where (a) the building is not more than 3 storeys in building height, (b) each guest suite is served by an exterior exit facility leading to ground level, (c) each guest suite is separated from adjacent rooms by a fire separation having a fire-resistance rating not less than 45 min, and (d) each guest suite is equipped with a smoke alarm. (3) A building is deemed to be in compliance with Sentence (1) where (a) the building is not more than 3 storeys in building height, (b) sleeping accommodation is provided for not more than 10 persons, and (c) the building is equipped with (i) smoke alarms on or near the ceiling in corridors serving guest suites on each floor area, adjacent to each stairway serving the corridors, and on or near the ceiling in the basement, adjacent to each stairway, and (ii) one manual pull station in each floor area in an approved location, installed and interconnected so that the actuation of any manual pull station or smoke alarm will cause all smoke alarms to operate and be audible throughout the building. Automatic detection
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.