fire code, O. Reg. 213/07

Section 9.9.3.14

Cite as fire code, O. Reg. 213/07, s. 9.9.3.14 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Emergency lighting shall be provided in (a) exits and access to exits in buildings required to have a fire alarm system, and (b) rooms containing an assembly occupancy with an occupant load of more than 60 persons. (2) Emergency lighting required in Sentence (1) shall be (a) designed to provide illumination for a duration of at least (i) 2 h in buildings where the vertical distance between the floor of the top storey and grade exceeds 18 m, and (ii) 30 min in buildings where the vertical distance between the floor of the top storey and grade is not more than 18 m, (b) supplied by a source of energy separate from the primary electrical supply for the building, and (c) designed to be automatically actuated when the power to the building is interrupted. (3) Illumination from emergency lighting referred to in Sentence (2) shall be an average of at least 10 lx at floor or tread level, or 1 watt/m2 of floor space. Subsection 9.9.4. Fire Alarm and Detection Fire alarm requirements