fire code, O. Reg. 213/07
Section 9.9.2.1
Cite as fire code, O. Reg. 213/07, s. 9.9.2.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Fire separations required by this Section to have a fire-resistance rating shall be in conformance with Subsection 3.1.7. and Articles 3.1.8.1., 3.1.8.2., 3.1.8.3. and 3.5.4.2. of the 1994 Building Code.
(2) If a fire-resistance rating of 2 h or less is required, existing wall assemblies, floor assemblies and their supporting assemblies are deemed to comply with Sentence (1) if they consist of
(a) reinforced concrete,
(b) masonry, or
(c) clay tile with plaster or gypsum board finish on both sides
(3) If a fire-resistance rating of 1 h or less is required, existing wall assemblies, floor assemblies, ceilings and their supporting assemblies that consist of membranes of lath and plaster or gypsum board are deemed to be comply with Sentence (1).
(4) Heavy timber construction conforming to Article 3.1.4.6. of the 1994 Building Code is deemed to have a 45 min fire-resistance rating.
(5) Buildings with limited combustible components may be approved as noncombustible construction.
(6) Except as permitted in Sentences (7) and (8), floor assemblies shall be fire separations.
(7) Sentence (6) does not apply to floor assemblies between different levels of the same multi-level guest suite.
(8) A floor assembly immediately above a crawl space is not required to be constructed as a fire separation and is not required to have a fire-resistance rating provided the crawl space is not considered as a basement in Sentence 3.2.2.5.(1) of the 1994 Building Code.
Buildings up to 3 storeys
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.