fire code, O. Reg. 213/07
Section 9.7.5.1
Cite as fire code, O. Reg. 213/07, s. 9.7.5.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) An automatic sprinkler system shall be installed in accordance with NFPA 13, “Standard for the Installation of Sprinkler Systems”
(a) in each building, or
(b) where a building is only partially occupied by a care occupancy or retirement home, on those storeys of the building that are occupied by the care occupancy or retirement home.
(2) Despite Sentence (1), in a building not greater than 3 storeys in building height that provides sleeping accommodation for not more than 10 persons, a sprinkler system may be installed in accordance with NFPA 13D, “Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes”, except that the minimum quantity of available water shall be adequate for a demand duration of at least 20 minutes if stored water is used as the sole water supply source.
(3) Despite Sentence (1), in a building not greater than 6 storeys in building height, a sprinkler system may be installed in accordance with NFPA 13R, “Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height”.
(4) An existing sprinkler system that provides an average sprinkler discharge density over a design area that is equal to the minimum density corresponding to the area for light hazard classification as defined in NFPA 13, “Standard for the Installation of Sprinkler Systems”, is deemed to be in compliance with Sentence (1).
(5) Sprinkler systems shall be equipped with local electric waterflow alarms.
(6) If a fire pump is required by NFPA 13 or NFPA 13R, it shall be installed in accordance with NFPA 20, “Standard for the Installation of Stationary Pumps for Fire Protection”, if it has a rated net head pressure greater than 280 kPa.
(7) Sentences (1) to (6) do not apply to a building not greater than 3 storeys in building height that provides sleeping accommodation for not more than four persons, if the building is equipped with smoke alarms that comply with Article 9.5.4.4. and that are interconnected so that the activation of any smoke alarm will sound a similar signal in each of the interconnected smoke alarms.
(8) Despite Clause (1)(b), installation of a sprinkler system is not required for those storeys containing the care occupancy or retirement home if the care occupancy or retirement home occupies not more than 10% of the floor area of the storey.