fire code, O. Reg. 213/07
Section 9.7.4.4
Cite as fire code, O. Reg. 213/07, s. 9.7.4.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) A voice communication system conforming to Article 3.2.4.22. of the 1990 Building Code shall be provided in every building where a floor area that is more than 18 metres above grade contains a care occupancy or a retirement home.
(2) A voice communication system is deemed to be in compliance with Sentence (1) if it
(a) consists of loudspeakers operated from,
(i) the central alarm and control facility, or
(ii) another location that is accessible to the fire department and supervisory staff required under Subsection 2.8.2. and that is approved,
(b) provides a clear verbal signal throughout the building, except within elevator cars, and
(c) provides for automatic silencing of the fire alarm devices when the loudspeakers are in use.
(3) A public address system capable of providing a clear verbal signal throughout the building, though not within elevator cars, is deemed to be in compliance with Sentence (1).
Subsection 9.7.5. Suppression
Sprinkler systems
Read the fire code on e-Laws ↗