fire code, O. Reg. 213/07

Section 9.7.3.1

Cite as fire code, O. Reg. 213/07, s. 9.7.3.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Emergency lighting shall be provided in exit stairways, public corridors and other principal access to exits. (2) The emergency lighting shall be (a) designed to provide illumination for a duration of at least 30 min, (b) supplied by a source of energy that is separate from the primary electrical supply for the building, and (c) designed to be automatically activated when the power to the building is interrupted. (3) The emergency lighting shall provide illumination that is at least an average of 10 1x at floor or tread level or at least 1 watt / m2 of floor space. (4) Sentence (1) does not apply in buildings 3 storeys or less in building height that provide sleeping accommodation for 10 or fewer persons. Subsection 9.7.4. Fire Alarm and Detection Fire signal to fire department