fire code, O. Reg. 213/07
Section 9.7.2.1
Cite as fire code, O. Reg. 213/07, s. 9.7.2.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Doors opening onto corridors that are access to exits and that serve resident suites, and resident sleeping rooms not within suites, in care occupancies and retirement homes shall be equipped with self-closing devices.
(2) Sentence (1) does not apply
(a) in buildings 3 storeys or less in building height that provide sleeping accommodation for 10 or fewer persons, and
(b) in buildings where all of the corridors referred to in Sentence (1) are subdivided in accordance with Sentence (3).
(3) The corridor subdivision referred to in Clause (2)(b) shall
(a) subdivide the corridor into at least two zones using fire separations that contain smoke-tight doors equipped with self-closing devices that act as closures,
(b) be arranged so that each subdivided corridor zone is able to accommodate, in addition to its own occupants, the occupants from any single adjacent zone, based on the requirements of 1.6 m2 per person, unless otherwise approved, and
(c) be arranged so that the travel distance from any point in a subdivided corridor zone to an adjacent zone is no more than 15 m.
Subsection 9.7.3. Means of Egress
Emergency lighting
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.