fire code, O. Reg. 213/07
Section 9.6.3.1
Cite as fire code, O. Reg. 213/07, s. 9.6.3.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Each dwelling unit or suite in a floor area shall have a doorway leading to
(a) the outside at or near grade,
(b) an outside passageway where it is possible to go in opposite directions to separate exits, or
(c) a public corridor where it is possible to go in opposite directions to separate exits.
(2) Access to exits through a dead end public corridor is deemed to be in compliance with Clause (1)(c) where the distance of travel, measured from any door along the corridor to a point where a choice of two directions of exit travel is available, does not exceed 6 m plus the width of the corridor.
(3) Existing dead end public corridors are deemed to be in compliance with Sentence (2) where additional fire protection measures are approved that, in the opinion of the Chief Fire Official, will provide protection for life safety similar to the protection provided by compliance with Sentence (2).
(4) Despite Sentence (1), if a dwelling unit or suite has access to a second and separate exit, a doorway from the dwelling unit or suite may open onto
(a) an exit stairway,
(b) a public corridor served by a single exit, or
(c) an outside passageway served by a single exit stairway.
Number of exits
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.